20 original questions. The keyed answer, the article to open, and a short explanation are on the page. Confirm the section in your NEC 2026 book. These items are a sample. The rest of this topic stays in the practice app.
All free sections·Study notes·20-question practice test
1 · Boxes and wiring methods · NEC Knowledge
The print calls for nonmetallic-sheathed cable on a run that passes through a wet location under a raised house, with the cable lying on the soil. The helper says the cable is fine wherever that product is customary. What should stop the installation?
Article 334 limits where nonmetallic-sheathed cable may be used. A wet location and a run lying on the soil are outside those permitted uses. Confirm the uses-not-permitted section in NEC 2026 before you treat a common indoor cable as an underground method.
Open NEC 2026 Article 334
2 · Boxes and wiring methods · NEC Knowledge
Nonmetallic-sheathed cable passes through a hole bored close to the face of a wood stud. In plain language, why would you add a steel plate there?
The plate is physical protection against fasteners that miss the stud center. It does not change ampacity and it does not ground the building. The bored-hole rules are in Article 300. Confirm the setback that triggers a plate in NEC 2026.
Open NEC 2026 Article 300
3 · Boxes and wiring methods · NEC Knowledge
A run of EMT is meant to be the equipment grounding path, and a set-screw coupling on that run is loose. What is wrong with that, in plain language?
A loose coupling breaks the metal path the fault would follow. EMT fittings have to keep that path intact when the raceway is the equipment grounding conductor. Article 358 covers the tubing and fittings. Article 250 is where you confirm that a raceway may serve as the grounding path.
Open NEC 2026 Article 358
4 · Boxes and wiring methods · NEC Knowledge
Pigtails that never leave this device box were each given a conductor volume allowance. The helper says every piece of copper in the box counts, including tails that start on the device and end in a wire nut. Which of those tails takes a volume allowance?
Article 314 gives no volume allowance to a conductor that starts inside the box and stays there. Confirm the conductor-count rules in NEC 2026. Do not add a cubic-inch total in this answer.
Open NEC 2026 Article 314
5 · Boxes and wiring methods · NEC Knowledge
Two internal cable clamps sit inside the box, and the helper counts two clamp allowances because he sees two clamps. Both clamps are the internal type the fill rule covers. He says each piece of hardware takes its own volume. What does the second clamp add?
Article 314 counts internal cable clamps as one volume allowance no matter how many of those clamps are in the box. Confirm the clamp rule in NEC 2026. Do not compute cubic inches here.
Open NEC 2026 Article 314
6 · Boxes and wiring methods · NEC Knowledge
A single-gang receptacle yoke was counted as one conductor because the helper says a device takes the same space as the one wire landed on it. The largest conductor on the device is the one he should have used, and he did not double it. What does that yoke count as?
Article 314 counts each device yoke as two volume allowances based on the largest conductor connected to that device. Confirm the yoke rule in NEC 2026. This question does not ask for a cubic-inch total.
Open NEC 2026 Article 314
7 · Boxes and wiring methods · NEC Knowledge
The helper embedded Type NM cable in the concrete slab and says the concrete protects the cable better than a raceway would. The cable is the ordinary dwelling NM, not a wiring method identified for embedment. What did the slab fail to legalize?
Article 334 does not permit Type NM cable to be embedded in concrete. Covering it is not a wiring method. Confirm the prohibited uses in NEC 2026.
Open NEC 2026 Article 314
8 · Boxes and wiring methods · NEC Knowledge
Small Type NM cable is stapled across the underside of the joists in an unfinished basement, perpendicular to the joists. The helper says any NM cable may be fastened to the bottom of a joist because the basement is unfinished and accessible. What size assumption did he skip?
Article 334 distinguishes which NM cables may be secured to the underside of joists and which must be bored or run on a running board. Confirm that distinction in NEC 2026. Do not invent the size cutoff in the answer.
Open NEC 2026 Article 314
9 · Boxes and wiring methods · NEC Knowledge
The fishing exception is the helper's reason for leaving a new NM run loose and exposed along an open basement wall. Nothing is concealed, and support is easy. He says once any cable may be fished, no NM cable has to be secured. Where does that exception stop?
Article 334 requires NM cable to be secured, and the fishing permission is a narrow case. An exposed basement run is not that case. Confirm the securing rules and the exception in NEC 2026. Do not invent the spacing.
Open NEC 2026 Article 314
10 · Boxes and wiring methods · NEC Knowledge
Type NM cable was pulled from the weatherhead to the service disconnect and used as the service-entrance conductors. The helper says NM is allowed on a dwelling, so it is allowed as the service cable too. What use did the dwelling permission fail to include?
Article 334 does not make Type NM cable a service-entrance wiring method just because the building is a dwelling. Confirm the permitted uses in NEC 2026.
Open NEC 2026 Article 314
11 · Boxes and wiring methods · NEC Knowledge
Lay-in ceiling support wires are holding the EMT. The helper clipped the raceway to the wires that support the ceiling grid and says metal wire is a listed hanger because it is already in the ceiling. What are those wires actually holding?
Article 300 does not let the EMT use the ceiling-grid support wires as its hanger unless the additional-support permission is actually met. Confirm that permission in NEC 2026.
Open NEC 2026 Article 314
12 · Boxes and wiring methods · NEC Knowledge
Aluminum EMT was buried in the earth and the helper says every EMT may be buried because it is a metal raceway. He did not select a steel product identified for earth contact. He treated the metal as interchangeable. What did the word EMT fail to settle?
Article 358 does not give every EMT metal the same permission in the earth. Confirm which product may be in earth contact in NEC 2026 before you bury this aluminum run.
Open NEC 2026 Article 314
13 · Boxes and wiring methods · NEC Knowledge
A loose set-screw coupling is the only equipment grounding path on this EMT run, and the helper says the pipe is metal so continuity does not depend on the coupling being tight. No separate equipment grounding conductor was pulled. What does the loose coupling fail to provide?
Article 358 can permit EMT to serve as the equipment grounding conductor only when the fittings maintain continuity. Confirm that condition in NEC 2026. Metal in the room is not the same as a tight coupling.
Open NEC 2026 Article 314
14 · Boxes and wiring methods · NEC Knowledge
Wire nuts join the conductors inside the wall cavity, with no box and no other enclosure. The helper says a splice in a concealed cavity is fine if the nuts are tight and the cable is NM. What is missing at the splice?
Article 300 requires a box or other permitted body where the conductors are spliced. Confirm the box requirement in NEC 2026. Tight wire nuts do not replace it.
Open NEC 2026 Article 314
15 · Boxes and wiring methods · Calculations
The problem prints the volume allowance: each 14 AWG conductor counts as 2.00 cubic inches. All equipment grounding conductors together count as one conductor. There is no device and no clamp. The box contains 8 conductors that each count, plus the equipment grounds. What minimum volume do you need?
Eight conductors plus one volume for all the grounds is 9. 9 × 2.00 = 18.00 cubic inches. Leaving the grounds out gives 16.00. On exam day the allowance comes from the box-fill table in Article 314. It is printed here so the count can be practiced.
Open NEC 2026 Article 314
16 · Boxes and wiring methods · Calculations
This drill says nonmetallic-sheathed cable is secured at intervals not greater than 4.5 ft. Both ends of this run are already secured at the boxes, and the boxes are 18 ft apart. Counting those two end supports, what is the fewest supports that keep every interval at 4.5 ft or less?
18 / 4.5 = 4 intervals, which takes 5 supports when both ends are included. Four supports would leave a gap larger than 4.5 ft. Confirm the securing distance for this cable in NEC 2026 Article 334. The 4.5 ft figure is printed in the stem.
Open NEC 2026 Article 334
17 · Boxes and wiring methods · Calculations
This drill counts 2.5 cubic inches per volume. There are 4 conductor volumes, 2 for the device, 1 for the equipment grounds, and 1 for the clamps. The box on the shelf is marked 18 cubic inches. How many cubic inches short of the count is that box?
Volumes: 4 + 2 + 1 + 1 = 8. 8 × 2.5 = 20.00 cubic inches. The box is 18, so it is 2.00 cubic inches short. Counting conductors only leaves the device, grounds, and clamps out. Article 314 is box fill. The 2.5 cubic inch figure is printed in the stem.
Open NEC 2026 Article 314
18 · Boxes and wiring methods · Calculations
A box contains 2 conductors at 3 cubic inches each and 4 conductors at 2.25 cubic inches each. The device allowance is 2 volumes and the equipment-grounding allowance is 1 volume, both counted at the larger conductor's 2.25 cubic inches. What is the minimum volume?
Small conductors are 2 × 3 = 6.00. Large conductors are 4 × 2.25 = 9.00. Device and grounds add 3 × 2.25 = 6.75. Total 21.75 cubic inches. Article 314 uses the larger conductor for the device and grounding allowances. The volumes are printed in the stem.
Open NEC 2026 Article 314
19 · Boxes and wiring methods · Calculations
This drill allows 360 degrees of bend between pull points. A crowded mechanical room already has bends of 90, 90, 90, and 165 degrees. How many degrees over 360 is that total?
90 + 90 + 90 + 165 = 435 degrees. 435 − 360 = 75. The run is 75 degrees over the drill, so you need another pull point. Confirm the bend total for the raceway in NEC 2026. The 360 degree limit is printed in the stem.
Open NEC 2026 Article 358
20 · Boxes and wiring methods · Calculations
This drill allows 0.75 square inches of conductor area. Each conductor takes 0.05 square inches, and the crew is pulling 18 of them. How many square inches over the allowance is that pull?
18 × 0.05 = 0.90 square inches used. 0.90 − 0.75 = 0.15 square inches over the allowance. The allowance itself is not the area you used. Confirm raceway fill in NEC 2026. Both figures are printed in the stem.
Open NEC 2026 Article 358