Articles 500 and 680 · free · no signup
20 original questions. The keyed answer, the article to open, and a short explanation are on the page. Confirm the section in your NEC 2026 book. These items are a sample. The rest of this topic stays in the practice app.
All free sections·Study notes·20-question practice test
1 · Special occupancies and equipment · NEC Knowledge
A room is marked Class I because a flammable vapor may be present. During normal operation the vapor is there often enough that the equipment has to be suited for that, not only for an accident. Which designation fits the normal-operation case?
Article 500 is where the class and division language starts. Division 1 is the normal-operation hazard. Division 2 is the case where the hazard shows up when something fails or is abnormal. Class II is combustible dust, not a vapor. Confirm the definitions in NEC 2026 before you pick a wiring method.
Open NEC 2026 Article 500
2 · Special occupancies and equipment · NEC Knowledge
In a Class I location, a flammable gas or vapor is expected in the air during normal operation, not only when equipment fails. Which designation fits that description?
Division 1 is the tighter Class I condition, where the hazard is expected in normal operation. Division 2 is where the hazard shows up mainly under abnormal conditions. Class III is fibers and flyings, not a gas. Article 500 sets out the designations. Read the descriptions in NEC 2026.
Open NEC 2026 Article 500
3 · Special occupancies and equipment · NEC Knowledge
An indoor spa is installed in a dwelling bathroom. The helper uses only the ordinary bathroom receptacle rules and skips the spa bonding and the receptacle rules written for the spa. Why is the bathroom rule not enough?
Article 680 covers indoor spas, including bonding and the receptacles around them. Article 210 still applies to the bathroom, but it does not replace the spa rules. Confirm the spa part of Article 680 in NEC 2026.
Open NEC 2026 Article 680
4 · Special occupancies and equipment · NEC Knowledge
The replacement pool pump was left on an ordinary breaker. The helper says the old pump never had ground-fault protection, so a replacement keeps that omission and only a new pool would need the device. What still protects the replacement?
Article 680 requires ground-fault protection for the pool pump motor. A previous omission does not become the rule for the replacement. Confirm the pump requirement in NEC 2026.
Open NEC 2026 Article 680
5 · Special occupancies and equipment · NEC Knowledge
This permanently installed gunite pool was called storable because the helper wanted to skip the bonding grid. The shell is part of the structure, not a seasonal product he can fold up. What label did he apply to the wrong pool?
Article 680 treats a permanently installed pool under the permanent-pool rules. Calling it storable does not change the shell. Confirm the storable-pool limits in NEC 2026 rather than inventing them.
Open NEC 2026 Article 680
6 · Special occupancies and equipment · NEC Knowledge
This indoor spa is treated as an ordinary bathtub. The helper says indoors means the bathroom receptacle rules are the only rules, and a spa inside the house has no pool-article duty. What did the roof over the spa fail to remove?
Article 680 still applies to this indoor spa. The bathroom branch-circuit rules do not replace it. Confirm the indoor spa requirements in NEC 2026.
Open NEC 2026 Article 680
7 · Special occupancies and equipment · NEC Knowledge
The concrete deck around this permanently installed pool was skipped for equipotential bonding. The helper bonded the pump motor only and says the deck is landscaping, not electrical equipment, so the perimeter is outside the grid. What surface is still part of the bond?
Article 680 includes the perimeter surface in the equipotential bonding of a permanently installed pool. Confirm how that surface is bonded in NEC 2026. The pump lug is not the whole grid.
Open NEC 2026 Article 680
8 · Special occupancies and equipment · NEC Knowledge
The poolside receptacle was spaced from the water with the kitchen-counter dimension the helper had memorized. He says a receptacle near water uses the kitchen rule, whether the water is a sink or a pool. What is wrong with that dimension?
Article 680 locates receptacles at a pool by its own distances. Confirm the real distance in NEC 2026. Do not treat the kitchen dimension as the pool rule.
Open NEC 2026 Article 680
9 · Special occupancies and equipment · NEC Knowledge
The hydromassage bathtub motor is supplied like a plain bathroom luminaire, with no ground-fault protection on the tub and no access left to the motor. The helper says the bathroom receptacle device covers every load in the room. What did that receptacle fail to cover?
Article 680 covers the hydromassage bathtub, including ground-fault protection and access to the motor. Confirm those rules in NEC 2026. The bathroom receptacle is a different outlet.
Open NEC 2026 Article 680
10 · Special occupancies and equipment · NEC Knowledge
The equipotential bonding conductor was sized from the equipment grounding conductor of the pump circuit. The helper says whatever ground fits the pump breaker is the bonding conductor for the whole pool. What sizing rule did the pump circuit fail to set?
Article 680 sizes the equipotential bonding conductor on its own terms. Confirm that conductor in NEC 2026. Do not copy the pump circuit's equipment grounding size and call it the bond.
Open NEC 2026 Article 680
11 · Special occupancies and equipment · NEC Knowledge
The helper left the equipotential conductor disconnected and says the pool water is conductive enough to be the bonding grid. The metal parts are not tied by a bonding conductor. What can the water not replace?
Article 680 requires the equipotential bonding means it describes. Pool water is not that conductor. Confirm the bonding means in NEC 2026.
Open NEC 2026 Article 680
12 · Special occupancies and equipment · NEC Knowledge
The pool water-heating equipment was left unbonded. The helper bonded the ladder and says heating equipment is a plumbing load, so it stays off the equipotential grid. The heater is part of the circulating-water system. What equipment is still on the bonding list?
Article 680 includes the electrical equipment associated with the water-circulating system in the equipotential bond. Confirm that list in NEC 2026. The ladder does not stand in for the heater.
Open NEC 2026 Article 680
13 · Special occupancies and equipment · NEC Knowledge
The helper placed the pool switching equipment at a distance he copied from a bathroom-zone habit and says any water uses that bathroom distance. He did not check the pool-equipment distance. Which number has to be confirmed before the switch stays there?
Article 680 sets where pool switching equipment may be placed. Confirm that distance in NEC 2026. A bathroom-zone habit is not the pool measurement.
Open NEC 2026 Article 680
14 · Special occupancies and equipment · NEC Knowledge
The equipotential grid is interrupted at a coupling the helper left open. He says a single break does not matter because the rest of the wire is in the deck. The parts on the far side of the break are not bonded. What does the open coupling destroy?
Article 680 requires the equipotential bonding system to be continuous to the parts it includes. Confirm the continuity rules in NEC 2026. A break in the deck is not a minor spare.
Open NEC 2026 Article 680
15 · Special occupancies and equipment · Calculations
This drill says metal parts within 5 ft horizontally of the inside wall of the pool are bonded. A ladder sits 4 ft from that wall. How many feet inside the 5 ft limit is the ladder?
5 − 4 = 1 ft inside the limit, so the drill includes the ladder. Adding the two distances gives 9 ft, which is not the question. Confirm the bonding distance in NEC 2026 Article 680. The 5 ft figure is printed here so the subtraction stands alone.
Open NEC 2026 Article 680
16 · Special occupancies and equipment · Calculations
A pool is a rectangle 20 ft by 40 ft. This drill asks for the length of a bonding conductor that follows the perimeter once, with no extra length for splices or connections. How many feet is that?
The perimeter is 2 × (20 + 40) = 120 ft. Adding the two sides once, without going all the way around, gives 60 ft. Article 680 describes the equipotential bonding conductor. The length in this item is the perimeter math from the dimensions in the stem.
Open NEC 2026 Article 680
17 · Special occupancies and equipment · Calculations
A lap pool pump full-load current is 24 A. Underwater lighting on the same equipment feeder is 12 A continuous. This drill takes both at 125%. Ground-fault protection is still required and does not change the ampacity. What feeder ampacity do you need?
Pump 24 × 1.25 = 30 A. Lighting 12 × 1.25 = 15 A. Total 45 A. The 250% figure is a motor short-circuit device, not this feeder ampacity. Article 680 still requires ground-fault protection for the pool equipment. It does not replace the ampacity math.
Open NEC 2026 Article 680
18 · Special occupancies and equipment · Calculations
Two pool pumps have full-load currents of 14 A and 8 A. An ozone generator on the same feeder is 4 A and runs more than 3 hours. Use 125% of the larger pump, 100% of the smaller pump, and 125% of the ozone generator. What feeder ampacity do you need?
14 × 1.25 = 17.5 A. The smaller pump stays 8 A. The ozone generator is 4 × 1.25 = 5 A. Total 30.5 A. Article 680 is the pool equipment. Article 430 is the several-motor pattern this drill is using. The factors are printed in the stem.
Open NEC 2026 Article 680
19 · Special occupancies and equipment · Calculations
A filter pump full-load current is 26 A. Conductors are 125%. The inverse-time breaker is 250% in this drill. Someone adds the two results together and calls that the wire size. What is the conductor ampacity alone?
Conductors are 26 × 1.25 = 32.5 A. The breaker is 26 × 2.50 = 65 A. Adding them double-counts two different Article 430 jobs. Article 680 does not replace that split, and it still requires ground-fault protection for the pool pump.
Open NEC 2026 Article 680
20 · Special occupancies and equipment · Calculations
A pool has 12 wet-niche luminaires at 200 W each on a 120 V circuit. Power factor is 1. The lighting is continuous, so this drill sizes the conductors at 125% of the combined current. What conductor ampacity do you need?
12 × 200 = 2,400 W. / 120 = 20 A. × 1.25 = 25 A. One luminaire's current is not the circuit. Article 680 covers the underwater luminaires, including the grounding rules that this ampacity step does not replace.
Open NEC 2026 Article 680